Home Contact Us
Parameter
HF 1000 R
HF 1000S
HF 5000S
Input
VA / W
1000 VA / 650 W
1000 VA / 700 W
5000 VA / 3000 W
Voltage
115 V / 230 V ± 15 %
110 V / 230 V ± 15 %
Frequency
50 Hz / 60 Hz ± 5 %
Phase
1 Ø 2W + G
Output
115 V / 240 V
Voltage Regulation
± 3 %
50 Hz / 60 Hz
Response
± 7 % @ ± 100 % on load
T.H.D
N/A
< 3 % @ 100% linear load
< 2 % @ 100% linear load
Waveform
Modified Sine Wave
Pure Sine Wave
Crest Ratio
3:1
Overload Capacity
105 % for 50 sec
Efficiency
System
> 83%
> 83 %
> 85 %
Inverter
> 90%
> 87 %
> 90 %
Battery
Load
650 W
700 W
100 W
3 kW
2.5 kW
1 kW
Backup Time
25 min
60 min
180 min
40 min
130 min
360 min
50 min
75 min
210 min
Recharge Time
1 ½ hrs 70 %
7 hrs 80 %
Transfer Time
AC Fail
0.1 s - 0.14 s
3 ms
3 ms – 5 ms
Bypass
< 0.1 s
< 4 ms
Audible Noise
@ 1 meter
< 45 dB
Indicators
LEDs
“LINE” “Battery in Use” “INV” “BYPASS” “FAULT” “Load Level” “Battery Level”
Environment
Temperature
0 ~ 40 oC
Humidity
30 % ~ 90 % (non-condensing)
Weight
kg (without batteries)
15.5 kg
15 kg
30 kg
Dimensions
W x H x D (mm)
210 x 450 315
330 x 390 x 430
390 x 680 x 750
Thermal Control
Cut-In Temperature
56 oC
Cut-Out Temperature
41 oC
Compliance
Standards
EN 50081 – 1, EN 50081 – 2, EN 50082 – 1, ANSI / IEEE 62.41
Copyright Sulfarid Technologies 2005